Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1) SINGLE GANG W/P BOX OUTSIDE KITCHEN DOOR OVER FILLED WITH CONDUCTORS, MUST HAVE 9 MAX BOX HAS OVER 12, SEE TABLE 370-16 B NEC 2) ALL SWITCHES MUST BE GROUNDED 380-9 B NEC |