Permit: T01EL00551

Parcel: 122163290


Addresses:

2311 N RICHEY BL #B


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL00551

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) SINGLE GANG W/P BOX OUTSIDE KITCHEN DOOR OVER FILLED WITH CONDUCTORS, MUST HAVE 9 MAX BOX HAS OVER 12, SEE TABLE 370-16 B NEC 2) ALL SWITCHES MUST BE GROUNDED 380-9 B NEC