Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 03/16/2001 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 03/09/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* 1994 NEC: 230.2 A BLDG SHALL BE SUPPLIED BY ONLY ONE SERVICE. 230.70 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN A BLDG. 225.37 ID ALL BRANCH, FEEDER, AND SERVICE DISCONNECTS. 225.30/225.33 ALSO ADDRESS # OF DISCONNECTS ALLOWED PER SUPPLY GROUP. 200.7 IMPROPER USE OF WHITE CONDUCTOR AS UNDERGROUND CONDUCTOR |
| 03/07/2001 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000$ PLEASE LEAVE ALL PAPER WORK HERE IN BOX. CANNOT MAKE PROPER INSP. DUE TO RAIN. WILL RESUME ASAP |