Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* OK WALLS | |
| 03/09/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) TIGHTEN ROMEX CLAMPS 2) STRAP ROMEX AS PER CODE 3) FHA STRAP IN CORNER DINNING ROOM (X) 4) GROUND METAL BOXES WHERE AVALIABLE 5) BATH GFI TO BE ON SEPERATE CIRCUIT NOT COOLER CIRCUIT 6) CK HALL SMOKE DETECTOR LOCATION |
|
| 03/02/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) NEED FHA STRAPS 2) SUPPORT ROMEX AS PER CODE 3) MAKE UP ALL BOXES 4) GROUND BOXES CORRECTLY 5) SUPPORT BOXES CORRECTLY 6) NEED 2 20 AMP APPLIANCE CIRCUITS 7) DUE TO THE AMOUNT OF CONSTRUCTION IN PROGRESS ALL WIRING TO MEET 1999 NEC REQUIREMENTS |