Permit: T01EL00415

Parcel: 131120720


Addresses:

5936 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000* NOTE: FINAL CONNECTION TO UTILITY IS SUBJECT TO APPROVAL OF RISER BY TEP
03/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0235* I COULD NOT FIND WHERE THE GROUND WIRE IS ATTACHED TO THE COLD WATER SERVICE PIPING. ALSO, BE ADVISED : THE 99 NEC NOW REQUIRES THE GAS PIPING ALSO TO BE BONDED TO THE MAIN PANEL. YOU MAY DO THIS BY BONDING THE GAS PIPE TO THE COLD WATER PIPE AT THE NEAREST POINT. INDICATE ON A PLAN / SHEET OF PAPER WHERE THE ABOVE GROUND BONDS ARE LOCATED RELATIVE TO THE HOUSE. PLEASE INSTALL YOUR METER INTO THE SOCKET. THE TAKING OF UNMETERED POWER IS PROHIBITED AND DANGEROUS