Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* NOTE: FINAL CONNECTION TO UTILITY IS SUBJECT TO APPROVAL OF RISER BY TEP |
| 03/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0235* I COULD NOT FIND WHERE THE GROUND WIRE IS ATTACHED TO THE COLD WATER SERVICE PIPING. ALSO, BE ADVISED : THE 99 NEC NOW REQUIRES THE GAS PIPING ALSO TO BE BONDED TO THE MAIN PANEL. YOU MAY DO THIS BY BONDING THE GAS PIPE TO THE COLD WATER PIPE AT THE NEAREST POINT. INDICATE ON A PLAN / SHEET OF PAPER WHERE THE ABOVE GROUND BONDS ARE LOCATED RELATIVE TO THE HOUSE. PLEASE INSTALL YOUR METER INTO THE SOCKET. THE TAKING OF UNMETERED POWER IS PROHIBITED AND DANGEROUS |