Permit: T01EL00368

Parcel: 127022150


Addresses:

5275 E BAKER ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/05/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/28/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1) SWITCHES FOR PATIO LIGHTS WITHIN 5' OF SPA NEED TO BE GFCI PROTECTED 2) GROUND IN SWITCH BOX SHOULD BE GREEN NOT WHITE
02/21/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* NOTES: INSTALL BOND BUSHING ON 1/2" NIPPLE AT SUB PANEL (CONCENTRIC KO). SUPPORT 1/2" CONDUIT NORTH OF FIRST 4/0 BOX AND WITHIN 36" EACH OTHER