Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/09/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) CHASE NIPPLES NOT APPROVED AT LB CONNECTIONS INTO PANELS 250 N.E.C. 2.) BOND BUSHINGS REQUIRED WHERE CONCENTRIC KO'S ARE USED AND SEALING LOCKNUTS ARE USED AND ASSCIATED ENCLOSURE FOR SERVICE 250-94 N.E.C 3.)INSTALL CONNECTORS WITH BUSHED ENDS WHERE ROMEX EXIT STEEL CONDUIT SLEEVES 300-15C 300-16 |
| 04/16/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* NOTES: OK TO CLEAR TEMP POWER, OK TO CABLE DROP, AND NEED TO INSP. AFTER TIE OVER WHEN READY |
| 04/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*BOND BUSHINGS OR LOCKNUTS REQUIRED PER 250-94 NEC. |