Permit: T01EL00356

Parcel: 12511140A


Addresses:

3603 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/09/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) CHASE NIPPLES NOT APPROVED AT LB CONNECTIONS INTO PANELS 250 N.E.C. 2.) BOND BUSHINGS REQUIRED WHERE CONCENTRIC KO'S ARE USED AND SEALING LOCKNUTS ARE USED AND ASSCIATED ENCLOSURE FOR SERVICE 250-94 N.E.C 3.)INSTALL CONNECTORS WITH BUSHED ENDS WHERE ROMEX EXIT STEEL CONDUIT SLEEVES 300-15C 300-16
04/16/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* NOTES: OK TO CLEAR TEMP POWER, OK TO CABLE DROP, AND NEED TO INSP. AFTER TIE OVER WHEN READY
04/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*BOND BUSHINGS OR LOCKNUTS REQUIRED PER 250-94 NEC.