Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/09/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*SEE WRITE UP TO1EL00356 AND T01EL00352 |
| 04/16/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* OK TO CLEAR TEMP POWER OK CABLE DROP |
| 04/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES: BOND LOCKNUTS FOR BUSHINGS REQUIRED PER 250-94 NEC. BOND GAS PIPING SYSTEM. |
| 04/10/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1) INSTALL PERMANENT ADDRESS LABELS, SCREWED OR RIVITED TO ENCLOSURE 2) ONE LINE DIAGRAM AND LOAD CALC'S APPROVED BY CITY PLAN CHECK 3) APPEARS THAT ONE SERVICE WAS SPLIT TO 5 SERVICES |