Permit: T01EL00352

Parcel: 12511140A


Addresses:

904 N RICHEY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/09/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) CHASE NIPPLES NOT ALLOWED AT TERMINATION INTO PANELS USE CLOSE NIPPLES LOCKNUT ON INSIDE AND OUT OF CABINATE AND BOND BUSHINGS OR BOND LOCKNUTS 250-94 NEC. 2.) INSTALL BOND BUSHINGS WHERE CONCENTRICS ARE USED. 3.) INSTALL CONNECTORS WITH BUSHED ENDS WHERE ROMEX EXITS STEEL CONDUIT SLEEVES 300-15 300-16 N.E.C
04/16/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* OK TO CLEAR TEMP POWER OK CABLE DROP
04/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES: BOND LUCKNUTS FOR BUSHINGS REQUIRED PER 250-94 NEC