Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/23/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* REQUIRE ELEC. CLEAN UP! 1) RESUPPORT PANEL AT 3732 MAIN HOUSE 2) PUT A PERMANENT ADDRESS ON EACH SERVICE 3) AT PANEL AT REAR STRUCTURE REGROUND SERVICE - 2 GROUND RODS AND WATER BOND AND GAS BOND 4) CLEAN UP AND CORRECT WIRING AT REAR STRUCTURE, PANEL INCORRECTLY WIRED 5) ALSO ALL 3 UNITS CAN BE ENERGIZED IF THIS ONE SERVICE RELEASED. NEED TO GET ADDITIONAL RECONNECT PERMITS FOR 1&3 6) MISSING BREAKERS OPEN METER DOUBLE LUGGING OBTAIN THE SERVICES OF AN ELEC. CONTRACTOR TO CORRECT. 7) INSTALL SMOKE DETECTORS IN ALL BEDROOMS |