Permit: T01EL00328

Parcel: 122152960

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) UNITS 1,2,3 ON OWNERS METER BASES WITH METERS CANNOT HAVE NEUTRALS BONDED INMETER BASES BECAUSE NEUTRALS ARE ALREADY BONDED AHEAD OF METER IN MAIN SERVICE ENTRANCE SECTION. 2) INSULATE NEUTRAL OFF OF METAL ENCLOSURES AND CALL FOR RE INSP.