Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/15/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) SUPPORT CONDUIT FROM CEILING OR REMOVE. 2) MISSING FACE PLATES 3) NEED APPROVED CONDUCTORS IN PANEL FOR ROMEX 4) DOUBLE LUGING OF NEUTRALS AND GROUNDS 5) SEAL DISCONNECT. 6) USE APPROVED LUGS AT DISCONNECT-NOT MODIFIED 7) CLEAN UP SERVICE AND PANELS 8) BOND WATER 9) MISSING FIXTURE END PLATES 10) NEED LIC. L-11 ELECTRICAL CONTRACTOR TO REPAIR WORK |