Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2001 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 02/15/2001 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* APPROVED ON SERVICE ONLY RELEASE OF POWER SUBJECT TO RAY CAMACHO COMPLAINT INSP. NOTE: NO HEAT IN HOUSE, BATHROOM AND KITCHEN SINK RECPTICALS TO BE GFI, BEDROOMS NEED SMOKE DETECTORS, AND PROPERLY DISCONNECT AND WIRE NUT WIRING IN DISCONNECT ABOVE REFRIGERATOR |
|
| 02/14/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) PANEL SHOULD NOT BE ENERGIZED, UNIT IS CONDEMNED BY CITY OF TUCSON(POSTED) 2) SERVICE WIDE OPEN - EXPOSED HOT PARTS, CORD BEING USED TO HEAT REAR UNIT, ALSO CONDEMNED. 3) NO ADDRESS ON SERVICE. 4) INCORRECT BREAKERS IN PANEL, OPEN WIRING. REMOVE ALL TEMP POWER 5) RISER NOT TO BE SUPPORTED WITH PLASTIC ANCHORS |