Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 03/15/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0230* 1) THE GROUND MUST CONSIST OF THE FOLLOWING ITEMS: 2-5/8X8 GROUND RODS SET 6' APART, THE COLD WATER PIPING AND THE GAS PIPING. 2) TEP REQUIRES A 2" MIN. SIZE PIPE RISER. SEE TEP SERVICE REQUIREMENTS BOOK SR-305 NOTE 5(PG3 OF 5) MARK ALL YOUR CIRCUIT BREAKERS |