| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. | |
| 04/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) INSTALL ROOF JACK FOR RISER CONDUIT. 2) INSTALL PERMANENT ADDRESS LABEL, SCREWED OR RIVITED, NO MARKING PEN. 3) GROUNDING ELECTRODE CONDUCTOR MUST BE UNSPLICED BETWEEN GROUND RODS, AND MUST BE CLAMPED PROPERLY. DO NOT USE BOTH SIDES OF CLAMP ON WATER AND GAS PIPING AS A MEANS TO SPLICE GROUNDING ELECTORDE CONDUCTOR 4) PROVIDE INFO CONCERNING THE NEW INTERIOR WIRING FOR HOUSE, SUCH AS PERMITS INSP. HISTORY. MAY BE IN VIOLATION OF CITY OF TUCSON UNIFORM ADMIN. CODE SEC #205 AND 301 5) INSTALL SEALING LOCKNUT OR HUBS AT PENETRATION, TOP OF PANEL. |
|
| 02/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0220* THE ELECTRICAL CODE, 1999 EDITION ART 250 NOW REQUIRES THAT THE ELECTRICAL SERVICE BE GROUNDED IN THE FOLLOWING MANNER: 1) THE COLD WATER PIPING 2) THE GAS PIPING 3) TWO GROUND RODS ( 5/8"X8') SET NO CLOSER THAN 6', AND DRIVEN TO 2" BELOW NATURAL GRADE. (DRAWING SUPPLIED ON INSP. SHEET) CORRECT AND RECALL LEAVE ENDS OF RODS EXPOSED |