Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTES: NEUTRAL CONDUCTOR TO GUEST HOUSE NEEDS TO BE INSULATED ENTIRE LENGTH, NOT 6" IN THE SERVICE, BARE CONDUCTOR NOT ALLOWED TO SERVE AS A NEUTRAL FOR FEEDER CIRCUITS | |
| 02/15/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) INSTALL INSULATED BUSHING ON CONDUIT CONNECTOR(1") 300-4-F NEC 2) BOND GAS PIPING 250-104 NEC 3) CONDUCTOR USED AS A NEUTRAL TO THE GUEST HOUSE SHOULD BE AN INSULATED CONDUCTOR IDENTIFIED AS SUCH |