Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/14/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* NOTES: BE CAUTIOUS OF NEXT SERVICE INSTALLATION OF OTHER UTILITIES IN OR CLOSE TO WORKING CLEARANCES PER NEC 110-26 |
| 02/09/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1) NEUTRAL TO BE BONDED AT ONLY 1 POINT AT SUPPLY OR CUSTOMER SIDE OF SERVICE, REMOVE NEUTRAL BOND TO GROUND AT EXIXTING DISCONNECT SWITCH BEYOND BREAKER PANEL. 2) ALSO BOND BUSHING REQUIRED IN METER END OF OFF SET NIPPLE OR BONDING TYPE LOCKNUT. 250-94 NEC. 3) K.O. ON BREAKER PANEL OFFSET NIPPLE APPEARS TO BE TOO BIG, INSTALL REDUCING WASHER. 4) BOND GAS PIPING 250-104 NEC. |