Permit: T01EL00275

Parcel: 127030910


Addresses:

5732 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000* NOTES: BE CAUTIOUS OF NEXT SERVICE INSTALLATION OF OTHER UTILITIES IN OR CLOSE TO WORKING CLEARANCES PER NEC 110-26
02/09/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) NEUTRAL TO BE BONDED AT ONLY 1 POINT AT SUPPLY OR CUSTOMER SIDE OF SERVICE, REMOVE NEUTRAL BOND TO GROUND AT EXIXTING DISCONNECT SWITCH BEYOND BREAKER PANEL. 2) ALSO BOND BUSHING REQUIRED IN METER END OF OFF SET NIPPLE OR BONDING TYPE LOCKNUT. 250-94 NEC. 3) K.O. ON BREAKER PANEL OFFSET NIPPLE APPEARS TO BE TOO BIG, INSTALL REDUCING WASHER. 4) BOND GAS PIPING 250-104 NEC.