Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0235* 1) THE GROUND WIRE MUST BE RUN UNSPLICED. 2) THE USE OF SPLIT BOLT CONNECTORS IS NOT ALLOWED. SPLICES MUST EITHER BE CAD WELDED OK JOINED BY APPROVED CRIMP FERCRULES |
| 02/21/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0225* THE 1999 NEC 250-104 REQUIRES THE COLD WATER AND GAS PIPING ALSO BE BONDED TO THE MAIN PANEL. THE GROUND RODS MUST BE SET 2" BELOW GRADE |