Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) BOND JUNCTION BOX 250-96 2) REMOVE OR BRING 2ND SERVICE UP TO CODE 3) NEED TO SEE PLANS FOR WORK BEING DONE ON INTERIOR 4) VERIFY LICENCED L-11 ELEC. CONTRACTOR | |
| 03/05/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) 2ND GROUND ROD TO BE MINIMUM 6' APART FROM 1ST ROD 2) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINIOUS 3) NEED PERMANENT METAL ADDRESS LABLES 4) STRAPS TO BE 1/4" HARDWARE MINIMUM 5) DNE WIRE PER LUG AT GROUND BAR 6) BOND JUNCTION BOX 250.96 7) BOND BOTH GAS SERVICES 8) REMOVE OR BRING 2ND SERVICE OF TO CODE |