Permit: T01EL00213

Parcel: 11904016B


Addresses:

3501 S 12TH AV

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Date Description Inspector Results Comments
12/20/2001 SIGN ELECTRIC Approved IVRS - Inspection 0000*
02/10/2001 SIGN ELECTRIC Denied IVRS - YOU MAY NOT RUN "ROMEX" INSIDE CONDUIT. REMOVE "ROMEX" AND INSTALL 3-#14 WIRES WITH 15 AMP BREAKER OR 3-#12 WIRES WITH 20 AMP BREAKER. YOU MUST USE RIGID METAL CONDUIT WHERE YOU ARE INSTALLING WIRING UNDER PARKING LOT. INSTALL MANUFACTURERS LABEL ON SIGN.