Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 01/30/2001 | ELECTRIC - FINAL | Partial Approval | RISER NEEDS 2 MORE PERMANENT STRAPS 1 AT MIDPOINT 1 W/IN 3' OF BOX NEED TO PERMANENTLY ADDRESS SERVICE NEUTRAL HAS TO HAVE TIE TO UFFER FROM RODS GET A FAULT CURRENT AVAILABLE AT TEP SUPPLY TO OK STANDARD SERVICE DRIVE GROUND RODS FLUSH TO GRADE ONLY 1 #4 WIRE ALLOWED ON EACH GROUND ROD CLAMP FIX #4 ENTRY INTO BOTTOM OF CAN WEST SIDE USE ROMEX CONNECTOR FIX COVER ON SERVICE SEAL HOLES BOTTOM SUB-PANEL AT STRUCTURE FIX 1 1/4" ENTRY INTO SUB PANEL WITH RE WASHERS |