Permit: T01EL00210

Parcel: 122070150


Addresses:

4425 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/20/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) EXPOSE SECOND GROUND ROD 2) ROMEX THRU WALL MUST BE BUSHED AT HOLE IN PANEL TO PROTECT FROM ABRASION.
3) #10 CONDUCTORS MUST HAVE WHITE INSULATION CONTINEOUS FOR BRANCH CIRCUIT WIRING 200-6 NEC
02/03/2001 ELECTRIC - FINAL Cancelled IVRS - Ri canceled