Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2008 | ELECTRIC - FINAL | Approved | ||
| 06/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LOCKNUTS BETWEEN PANEL & METER NOT WRENCH TIGHT 2. 1 1/2" CONDUIT TO INSIDE BLD. NOT SUPPORTED 3. CANNOT VERIFY GROUNDING 4. REMOVE PANEL DEAD FRONT 5. CIRCUIT BRKS MUST BE SAME AS PANEL MANUF. BRAND |
|
| 02/02/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* SERVICE UPGRADE/NEW PARTIAL NEED TO HAVE T.EP. VERIFICAITON OF AVAILABLE FAULT CIRCUIT AT METER TERMINALS |
|
| 02/01/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0220* ADDITIONAL GROUND BONDING AT NIPPLE, SUPPORTING IRON FRAME WORK , AND PREMISES GAS PIPING IS REQUIRED NEC 250-104 |