Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/26/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* UNIT LOCKED MUST BE OPEN FOR INSPECTION INSTALL FORNT PORCH LIGHT ADDRESS SERVICE PERMANENTLY, STRAP GROUND WIRE AT SERVICE TO WALL HOUSE IS NOT FULLY WIRED ONLY HAS 2-20 AMP CIRCUITS TO IT. SEVERAL CIRCUITS MISSING, SEVERAL CIRCUIT BREAKER SLOTS OPEN MAIN 100 AMP CIRCUIT BREAKER MUST BE CHIPPED OR BOLTED DOWN USE A ROMEX CONNECTOR WHERE GROUND WIRE ENTERS BOTTOM OF THE SERVICE REPAIR OUTSIDE REAR PORCH LIGHT SUGGEST YOU HAVE A LICENSED ELECTRICAL CONTRACTOR MAKE ALL REPAIRS AND RECALL FOR INSPECTION M |