Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/25/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* A SEAL OFF REQUIRED IMMEDIALITY EMERGING FROM THE GROUND. A SEAL OFF REQUIRED W/IN 18" OF THE EXPOLSION PROOF ENCLOSURE NO STANDARD COUPLING ALLOWED BETWEEN THE SEAL OFF AND THE EXPLOSION PROOF ENCLOSURE OK TO COVER HOLES PROVIDED OTHER INSPECTION APPROVED |