Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0225* 1) THERE ARE MANY LIGHTING FIXTURES MISSING. THE WIRES MUST BE CAPPED AND TUCKED INTO THE BOXES OR INSTALL NEW FIXTURES. 2) SEVERAL PLUGS AND SWITCHES ARE MISSING RETAINING SCREWS AND FACE PLATES 3) THE BATHROOM NEEDS A GFT RECEPTICLE 4) SUGGEST SMOKE DETECTORS BE INSTALLED IN HALL 5) THE ELECTRIC SERVICE GROUNDING WIRE AND CLAMPS ARE LOOSE. INSTALL NEW CLAMPS AND GROUND THE COLD WATER AND GAS PIPE TO THE PANEL | |
| 02/01/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* DENIED ALL DOORS AND GATES LOCKED RE FEE DUE |
|
| 01/25/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* PLEASE BE ON THE PROPERLY FOR THE INSPECITON. IT IS NECESSARY THAT THE INSPECTOR ENTERS INTO THE HOUSE TO CHECK ALL VITAL ELECTRICAL ITEMS REQUIRED FOR SAFE USE OF THE HOUSE, YOU MAY ALSO LEAVE THE HOUSE UNLOCKED AND LEAVE A NOTE WITH ANY INSTRUCTIONS OR QUESTIONS YOU MAY HAVE |