Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 02/06/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* FEEDERS TO MULTIPLE DISCONNECT SWITCHES IN 4" CONDUIT FROM CT CAN MUST BE DE-RATED 11-4" CONDUIT HAS 9 UNGROUNDED CONDUCTORS MUST BE DE-RATED TO 70% 11-4" CONDUIT HAS 6 UNGROUNDED CONDUCTORS MUST BE DE-RATED TO 80% NEC 310-15 B UFER GROUNDING ELECTRODE SYSTEM AND CONDUCTOR WAS NOT INSPECTED PRIOR TO COVERING AC LINES AND AC FEEDER CIRCUITS POSE A TRIP HAZARD IN FRONT AND AROUND SERVICE EQUIPMENT 110-26 NEC |