Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 01/17/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0220* BE ADVISED THE 1999 NEC REQUIRES THE BONDING OF THE GAS AND WATER LINES TO THE MAIN PANEL NEUTRAL BAR. THE GROUND WIRE MUST BE THE SAME SIZE AS THE "UFER" CONDUCTOR CORRECT AND RECALL |