Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 01/23/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* NEED 2- SUPPORTS ON RISER BELOW ROOF LINE GROUND ROD TO BE DRIVEN STRAIGHT DOWN FIRST UNLESS ROCK IS ENCOUNTED AND THEN AT A 45 DEGREE ANGLE SECOND NOT AT A 30 DEGREE ANGLE BOND DEVICE NEEDED AROUND REDUCING WASHERS BOND JUNCTION BOX |