Permit: T01EL00077

Parcel: 125050930


Addresses:

2328 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/22/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
01/18/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
INSTALL BOND BUSHINGS ON CONNECTORS
ENTRANCES AT CONCENTRIC KO'S NEC. NEC 250-94
CHASE NIPPLE NOT APPROVED ON 1/2 LB
USE CLOSE NIPPLE WITH LOCKNUTS/ BUSHING
RE SUPPORT RISER, BOTTOM SUPPORT PULLING OUT, USE MIN 1/4" ANCHORS
MMISSING LB COVER
PLUG FOR W/P BOX

BOND GAS PIPING, NEC 250-104