Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL00018
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
09/21/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*1.) WORK FROM PREVIOUS INSPECTION NOT COMPLETED NO WORK PROGRESS 2.) UNSAFE WIRING METHOD AND EXPOSED CONDUCTORS. | |
08/23/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1. INSULATION AT SPLICE CONNECTOR TO BE AS CODE 110-14(B) 2. BOND SUB PANEL ENCLOSURE. OK TO CLEAR FOR POWER, * NOTE: 10 DAY FOLLOW-UP | |
08/20/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED FILLER BLANKS 2.) MISSING DEAD FRONT SCREWS 3.) BREAKER LABELED DRYER WITH 1 POLE 15 AMP BREAKER USE CORRECT BREAKER OR RE LABEL. 4.) TAP IN SUB PANEL NOT MADE UP CORRECT USE CORRECT SIZED WIRE SPLIT BOLT ONLY LISTED FOR 2 WIRES A RUN AND A TAP USE CORRECT SPLICE METHOD 5.) MISSING A SCREW IN LB COVER 6.) VERIFY 2ND GROUND ROD. 7.) WHICH SERVICE IS CONNECTED ON THIS PERMIT #1 OR #2 HAVE PERMIT TO REFLECT WHICH SERVICE. | |
02/05/2001 | ELECTRIC - FINAL | Partial Approval | 1) SEAL ALL UNUSED OPENINGS IN PANEL 2) FINISH DRIVING GROUND ROD'S 8' TO BE IN CONTACT WITH EARTH 3)LABEL ALL BREAKERS 4) WHAT ARE CONDUCTORS FOLDED BACK AT CHASE NIPPLE FOR? |