Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01EL00018

Parcel: 115043790

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL00018

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
09/23/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
09/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*1.) WORK FROM PREVIOUS INSPECTION NOT COMPLETED NO WORK PROGRESS 2.) UNSAFE WIRING METHOD AND EXPOSED CONDUCTORS.
08/23/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. INSULATION AT SPLICE CONNECTOR TO BE AS CODE 110-14(B) 2. BOND SUB PANEL ENCLOSURE. OK TO CLEAR FOR POWER, * NOTE: 10 DAY FOLLOW-UP
08/20/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) NEED FILLER BLANKS 2.) MISSING DEAD FRONT SCREWS 3.) BREAKER LABELED DRYER WITH 1 POLE 15 AMP BREAKER USE CORRECT BREAKER OR RE LABEL. 4.) TAP IN SUB PANEL NOT MADE UP CORRECT USE CORRECT SIZED WIRE SPLIT BOLT ONLY LISTED FOR 2 WIRES A RUN AND A TAP USE CORRECT SPLICE METHOD 5.) MISSING A SCREW IN LB COVER 6.) VERIFY 2ND GROUND ROD. 7.) WHICH SERVICE IS CONNECTED ON THIS PERMIT #1 OR #2 HAVE PERMIT TO REFLECT WHICH SERVICE.
02/05/2001 ELECTRIC - FINAL Partial Approval 1) SEAL ALL UNUSED OPENINGS IN PANEL
2) FINISH DRIVING GROUND ROD'S 8' TO BE IN CONTACT WITH EARTH
3)LABEL ALL BREAKERS
4) WHAT ARE CONDUCTORS FOLDED BACK AT CHASE NIPPLE FOR?