Permit: T01EL00010

Parcel: 121091990

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR CORRECTIONS OK
01/24/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0910*
NO ACCESS DUE TO LOOSE DOGS IN YARD, PREVIOUS INSPECTION WRITE-UP WARNS ABOUT RE-FEE.
PLEASE PAY RE-FEE 201 N STONE BEFORE CALLING FOR RE-INSPECTION. LOCK UP DOGS OR HAVE OWNER HOME FOR NEXT INSPECTION
01/17/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
NOTES
INSULATING BUSHING REQUIRED #4
OR LARGER CONDUCTORS, 300-45 NEC
SPLIT BOLT TYPE SPLICE NOT APPROVED IN SUB PANEL OUTSIDE APT APPLY ANTI OXIDENT COMPOUND ON ALL ALUMINUM TERMINATIONS
01/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0910*
COULD NOT ENTER YARD DUE TO LOOSE DOGS
LAST FINAL INSPECTION WAS NOT READY, A RE-INSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NOT READY OR NO ACCES TO SITE
01/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
INSTALL PERMENENT ADDRESS LABEL NEC 230-70 #9287 CITY ORDIN
SUPPORT 1 1/2" CONDUIT WITHIN 3' OF ENTRY TO SERVICE AND AT 10' INTERVALS, 348-13 NEC
BOND BUSHINGS OR BOND LOCKNUTS REQUIRED NEC 250-94
COMPLETE WIRING TO APT
BOND GAS PIPING SYSTEM TO SERVICE 250-104 NEC