Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR CORRECTIONS OK |
|
| 01/24/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0910* NO ACCESS DUE TO LOOSE DOGS IN YARD, PREVIOUS INSPECTION WRITE-UP WARNS ABOUT RE-FEE. PLEASE PAY RE-FEE 201 N STONE BEFORE CALLING FOR RE-INSPECTION. LOCK UP DOGS OR HAVE OWNER HOME FOR NEXT INSPECTION |
|
| 01/17/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTES INSULATING BUSHING REQUIRED #4 OR LARGER CONDUCTORS, 300-45 NEC SPLIT BOLT TYPE SPLICE NOT APPROVED IN SUB PANEL OUTSIDE APT APPLY ANTI OXIDENT COMPOUND ON ALL ALUMINUM TERMINATIONS |
|
| 01/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0910* COULD NOT ENTER YARD DUE TO LOOSE DOGS LAST FINAL INSPECTION WAS NOT READY, A RE-INSPECTION FEE WILL BE ASSESSED NEXT INSPECTION IF NOT READY OR NO ACCES TO SITE |
|
| 01/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* INSTALL PERMENENT ADDRESS LABEL NEC 230-70 #9287 CITY ORDIN SUPPORT 1 1/2" CONDUIT WITHIN 3' OF ENTRY TO SERVICE AND AT 10' INTERVALS, 348-13 NEC BOND BUSHINGS OR BOND LOCKNUTS REQUIRED NEC 250-94 COMPLETE WIRING TO APT BOND GAS PIPING SYSTEM TO SERVICE 250-104 NEC |