Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM06224
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
05/15/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) COLOR CODING INCORRECTION WIRING INSULATION INSTALL PROPERLY COLORED CONDUCTORS PER N.E.C. AND #9287 CITY ORDIN. | |
05/10/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTES 1.) NEW X FORMER TO BE GROUNDED PER NEC. 250-30. 2.) NEED TO INSPECT CONNECTIONS INSIDE X FORMER AND SUB PANEL. | |
04/16/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) COMPLETE ELECTRICAL INSTALLATONS FOR UPS SYSTEMS. |