Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM06215
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*FINAL SUBJECT TO OTHER INSPECTION. | |
03/01/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*CONTRACTOR COULD NOT FIND REPORT OF PREVIOUS DAY INSPECTION REISSURED LAST INSPECTION NOTICE OF 2/28/01 | |
02/28/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*3 WAY SWITCHES NOT 20 AMP OR 277 V. RATED COMPLETE OFFICE PARTITION. OPEN ELECTRIC ROOM TO FIND CIRCUITS AND NEED TO SEE HOW ISOLATION OF RECEPT CIRCUITS FOR ISO. SYS) WAS ACCOMPLISHED FLUSH OUT RECEPT BEHIND CABINET. FINAL SUBJECT TO OTHERS INSPECTION NEED TO SEE HOT DISCONNECTING. |