Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*FINAL SUBJECT TO OTHER INSPECTION. |
| 03/01/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*CONTRACTOR COULD NOT FIND REPORT OF PREVIOUS DAY INSPECTION REISSURED LAST INSPECTION NOTICE OF 2/28/01 |
| 02/28/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*3 WAY SWITCHES NOT 20 AMP OR 277 V. RATED COMPLETE OFFICE PARTITION. OPEN ELECTRIC ROOM TO FIND CIRCUITS AND NEED TO SEE HOW ISOLATION OF RECEPT CIRCUITS FOR ISO. SYS) WAS ACCOMPLISHED FLUSH OUT RECEPT BEHIND CABINET. FINAL SUBJECT TO OTHERS INSPECTION NEED TO SEE HOT DISCONNECTING. |