Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 01/23/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*CONNECT THE BARE GROUNDING CONDUCTOR TO THE MAIN GROUND STRIP OR PROVIDE A #4 JUMPER BETWEEN THE TWO STRIPS. 2.) GROUND RODS MUST BE A MINIMUM OF 6' APART. DO NOT BEND RODS TO ACHIEVE THIS DISTANCE. THEY CAN BE MORE THAN 6' APART. NOT LESS REMOVE AND RE-INSTALL OR INSTALL A NEW ADDITIONAL ROD. |