Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T01CM06182

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000* PROVIDE A LETTER FROM THE ENGINEER ABOUT THE FLEX DUCT THREE THE GARAGE FIRE WALL. NO METAL DUCT? NO FIRE DAMPER? OK FOR SHEET ROCK.
05/23/2002 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*PROVIDE BACKING AROUND CEILING BOXES. 2) PROVIDE LETTER FROM ENGINEER ABOUT FLEX DUCT IN THE GARAGE PLANS CALL FOR 26 GA. DUCT. 3.) TOP PIECE OF FIRE PLACE FLUE NOT ATTACHED PROPERLY. WILL CHECK ON FINAL 4.) PROVIDE MIN 2" CLEARANCE AROUND FIRE PLACE VENT PIPE. 5.) IS WALL BETWEEN GARAGE BEDROOM FIRE RATED? IF SO WHERE ARE THE FIRE DAMPERS.