Permit: T01CM06181

Parcel: 112050670


Addresses:

3002 N CAMPBELL AV


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T01CM06181

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2002 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) THIS INSPECTION IS FOR RM 108,117,ONLY 3.) NOTE: EXSISTING BLDG. DRAIN WILL NOT HOLD WATER TEST. DUE TO CRACKS IN CAST IRON. WILL REQUIRE A NEW 4" BLDG. DRAIN 4.) WILL REQUIRE A REVISED AND APPROVED DRAWINGS ON NEW 4" BLDG DRAIN PRIOR TO NEXT INSPECTION 5.) OK TO BACKFILL TRENCH.
02/04/2002 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection 0999*JOB SITE TRAILER WAS LOCKED NO ACCESS TO APPROVED PLANS.