Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM06177
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2002 | MECHANICAL - FINAL | Approved | OK FOR C OF O. | |
02/12/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*#8 WIRE NOT ADEQUATE SIZE FOR 60 AMP CIRCUIT TO AC UNITS. 2.) LABELS EQUIPMENT ON ROOF. 3.) PROVIDE OUTSIDE AIR VENTS ON AC UNITS RECALL FOR FINAL. |