Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM06177
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
01/17/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* 1.) 4 SQUARE BOXES OVEFILLED. SEE ART 370-16A N.E.C. 2.) PLANS NEED TO BE ON SITE. 3.) LIGHT FIXTURES NOT INSTALLED. | |
01/16/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*NOTES MC CABLE AND EMT CONDUIT TO BE SUPPORTED PER N.E.C. |