Permit: T01CM06149

Parcel: 133541730

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM06149

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2002 FRAMING Approved IVRS - Inspection 0000*
02/05/2002 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) REMOVE SCREEN FROM DRYER VENT 2) REMOVE NAILS FROM JOISTS TO TRUSSES AT PATIO CONNECTION 3) OK TO INSULATE
02/01/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) NO WATER TEST ON TOP OUT 2) PROVIDE OR REPLACE ENGINEERING FOR NOTCHED BEARING WALLS 3) REMOVE SCREEN FROM DRYER VENT 4) ADD STUD LEFT OR RIGHT SIDE OF HOOD VENT 5) ADD 16 GAUGE STRAP WITH 6-16D NAILS EACH SIDE AT KITCHEN 6) REMOVE NAILS FROM PORCH JOIST TO TRUSSES AND INSTALL H2.5 AS PER DETAIL #6 PG A8 7) PROVIDE DETAIL SHOWING INTERIOR WALLS NAILING TO BOTTOM TRUSS CHORD 8) PROTECT COPPER WATER LINES AT LAUNDRY ROOM 9) PEX WATER