Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/05/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) RANGE GAS VALVE MUST BE INSTALLED AND RANGE CONNECTED OR SOV CAPPED 2) CANNOT TEST ELECTRIC CIRCUITS UNTIL CONNECTED TO TEP POWER 3) RANGE HOOD NOT INSTALLED 4) KITCHEN COUNTER AT NORTHEAST CORNER OF KITCHEN HAS COUNTER TOP MORE THAN 24" FROM OUTLET GFCI 5) GFCI ELECTRIC OUTLET REQUIRED WITHIN 24" OF LEFT SIDE OF KITCHEN SINK 6) WASHING MACHINE DRAIN MUST BE 2"-1 1/2" INSTALLED 7) LAUNDRY TRAP EXCEEDS 60" TO VENT 8) FIREPLACE GAS LOG REQUIRES GAS PLUMBING HARD PIPE AND SHUT OFF VALVE INSTALLED INSIDE 9) FIREPLACE OPENING EXCEEDS 6 SQUARE FEET REQUIRES 20" HEARTH ON 3 SIDES 10) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS 11) PLUG OPEN KNOCKOUTS IN SERVICE PANEL |
| 01/31/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0935*/ 1) HOUSE MUST BE COMPLETE AND READY TO OCCUPY PRIOR TO FINAL INSPECTION 2) YOU ARE STEALING ELECTRIC POWER. TEP HAS BE NOTIFIED, REFEE MUST BE PAID BEFORE NEXT INSPECTION |
| 01/30/2002 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |