Permit: T01CM06139

Parcel: 113021850


Addresses:

1020 E KING ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/11/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/05/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) RANGE GAS VALVE MUST BE INSTALLED AND RANGE CONNECTED OR SOV CAPPED 2) CANNOT TEST ELECTRIC CIRCUITS UNTIL CONNECTED TO TEP POWER 3) RANGE HOOD NOT INSTALLED 4) KITCHEN COUNTER AT NORTHEAST CORNER OF KITCHEN HAS COUNTER TOP MORE THAN 24" FROM OUTLET GFCI 5) GFCI ELECTRIC OUTLET REQUIRED WITHIN 24" OF LEFT SIDE OF KITCHEN SINK 6) WASHING MACHINE DRAIN MUST BE 2"-1 1/2" INSTALLED 7) LAUNDRY TRAP EXCEEDS 60" TO VENT 8) FIREPLACE GAS LOG REQUIRES GAS PLUMBING HARD PIPE AND SHUT OFF VALVE INSTALLED INSIDE 9) FIREPLACE OPENING EXCEEDS 6 SQUARE FEET REQUIRES 20" HEARTH ON 3 SIDES 10) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS 11) PLUG OPEN KNOCKOUTS IN SERVICE PANEL
01/31/2002 BUILDING - FINAL Denied IVRS - Inspection 0935*/ 1) HOUSE MUST BE COMPLETE AND READY TO OCCUPY PRIOR TO FINAL INSPECTION 2) YOU ARE STEALING ELECTRIC POWER. TEP HAS BE NOTIFIED, REFEE MUST BE PAID BEFORE NEXT INSPECTION
01/30/2002 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*