Permit: T01CM06136

Parcel: 128090020

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
02/20/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
02/19/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*1.) TRACK LITING REQUIRES TWO SEISMIC WIRES PER TRAC. 2.) COMPLETE FLOOR RECEPS. & WIRING EXTENSIONS TO COUNTER. 3.) CONNECT ALL EMERGENCY LITING "BATTERY PAKS & PREPARE FOR TEST. 4.) MAKE SURE ALL EXIT SIGNS ARE PLUGGED INTO BATTERY BACK UP & TEST.
02/15/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*NOT READY.