Permit: T01CM06125

Parcel: 13303244B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/30/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) VERIFY GROUNDING CONDUCTORS ARE ATTACHED TO ALL METALLIC BOXES 2) PROVIDE GROUNDING SYSTEM: EITHER GROUNDING CONDUCTOR FROM EXISTING SERVICE OR 2 GROUND RODS WEST #4 CONTINOUS COPPER CONDUCTOR TO NEW SERVICE GROUND RODS MUST BE A MINIMUM OF 6' APART