Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/16/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O. |
| 07/09/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) 1ST SECTION OF CONDENSATE DRAIN LINE SLOPE THE WRONG DIRECTION PROVIDE MIN 1/8" PER FT. SLOPE LONG LENGTH OF DRAIN BARELY MEETS CODE. 2.) PROVIDE A SECONDARY DRAIN PAIN. DRAIN TO A CONSPICUOUS LOCATION 3.) PROVIDE REMOVABLE ACCESS COVERS FOR FILTER. OK FOR PARTIAL CEILING TILES. |