Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM06091
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O. | |
07/09/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) 1ST SECTION OF CONDENSATE DRAIN LINE SLOPE THE WRONG DIRECTION PROVIDE MIN 1/8" PER FT. SLOPE LONG LENGTH OF DRAIN BARELY MEETS CODE. 2.) PROVIDE A SECONDARY DRAIN PAIN. DRAIN TO A CONSPICUOUS LOCATION 3.) PROVIDE REMOVABLE ACCESS COVERS FOR FILTER. OK FOR PARTIAL CEILING TILES. |