Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T01CM06091

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O.
07/09/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) 1ST SECTION OF CONDENSATE DRAIN LINE SLOPE THE WRONG DIRECTION PROVIDE MIN 1/8" PER FT. SLOPE LONG LENGTH OF DRAIN BARELY MEETS CODE. 2.) PROVIDE A SECONDARY DRAIN PAIN. DRAIN TO A CONSPICUOUS LOCATION 3.) PROVIDE REMOVABLE ACCESS COVERS FOR FILTER. OK FOR PARTIAL CEILING TILES.