Permit: T01CM06066

Parcel: 12009001B


Addresses:

420 E AVIATION DR

Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/06/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NEED TO COMPLY WITH ITEM #5 VAST INSPECTION, 2 HOLE MECH LUGS TO BE INSTALLED PER DESIGN & LISTING.
10/25/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
10/23/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.)PERMANENTLY IDENTIFY MAIN SERVICE PER PLAN S.E.S. LARGE LETTERS PLEASE. 2.) PERMANENTLY IDENTIFY FEEDER BREAKER AT S.E.S. THAT GOES TO D.S.B.B. 3.) PERMANENTLY LABEL PER PLAN DSBB LARGE LETTERS. 4.) NEED COMPANY LETTERHEAD FROM LICENSED L-11 K-11 CONTRACTOR STATEING THAT ALL TERMINATION HAVE BEEN TORQUED PER MANUFACTURE SPECIFICIATION. 5.) AT GUTTER NEED TO HAVE FULL CONTACT ON TANGS OF ALL LUGS. DO NOT STACK LUGS. 6.) DISTANCE BETWEEN LIVE BAR CONDUCTORS AND GROUNDED OBJECTS @ 480/277 NOT SUFFICIENT DISTANCE. 1/2" 7.) CHECK BUS BAR FOR 1200 AMP CAPACITY. 8.) USE TYRAPS OR OTHER ACCEPTABLE/APPROVED MEANS TO BRACE CONDUCTOR. DO NOT USE WIRE ITSELF. 9.) NEUTRAL IS BONDED AT DISCONNECTS OUT OF 12X12 WIREWAY, MUST BE ISOLATED 10.) PLEASE HAVE ACCURATE PLANS. 11.) WILL NEED A LISTING FOR PLASTIC CONTROLLER #2. AND ALL OTHER EQUIPMENT READY FOR USE.