Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM06001
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
02/06/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) SERVICE DOES NOT REFLECT PLANS PLEASE PROVIDE REVISED APPROVED PLAN OR INSTALL AS PER PLANS. | |
02/05/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) LABELING NEED TO BE PERMENT PLASTIC LAEL DO NOT MEET UV REQUIRMENT AND WILL DETERATE 110-22. 2.) CLEAN SURFACE BEHIND LUG 250-12. 3.) PLEASE MAINTANCE WIRE BENDING RADIOSES "A" PHASE LINE/LOAD 373-6.4.) PLEASE ACCUIRE ACCESS TO GUTTER FOR BONDING INSPECTION. | |
01/31/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) DISCONNECT ENCLOUSERS NEED TO BE BONDED PLEASE INSTALL BOND SCREWS. 2.) COOLER DISCONNECT NEED TO BE LABELED 3.) SURFACE BEHIND GROUND LUG NEED TO BE CLEANED OF PAINT 250-12 4.) PLEASE COMLETE CROSS OVER FIRST. |