Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05999
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL STOI | |
02/06/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SERVICE DOES NOT REFLECT PLANS. PLEASE PROVIDE REVISED APPROVED PLANS OR INSTALL AS PER PLANS. | |
02/05/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PLEASE PROVIDE REJECTION PINS. 2.) A BUSHING IS NEEDED TO PROTECT CONDUCTORS ENTERING THE FITTING 300-15 (C). 3.) PLEASE HAVE PLANS ON SITE I NEED TO VERIFY INFORMATION. 4.) LABELING NEED TO BE PERMANENT PLASTIC LABELS DO NOT MEET UV REQUIREMENTS AND WILL DETERATE 110-22. | |
01/31/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) CONDUIT RUNS CAN HAVE MORE THAN 360 OF BEND. 2.) SUPPORT CONDUIT WITHIN 3' OF BOXES AND FITTING 348-18 3.) PLEASE LABEL COOLER DISCONNECTS AND TIGHTEN GROUND SCREWS. 4.) SERVICE IS NOT READY. |