Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM05999
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
01/13/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*RECEIVED LETTER AUTHURIZING. M/C CABLE AND 1/2" CONDUIT 1.) WORKING CLEARENCE TO BE THE WIDTH OF SERVICE. | |
01/10/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) NEED LETTER AS PER LAST INSPECTION OK BATH ROOM WALLS AND HARD CEILING. | |
01/08/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) MC CABLE NOT SUPPORTED PROPERLY ON BATHROOM CEILINGS.2.) REMOVE INSULATION TO INSPECT CONDUIT RUNS ON CENTER WALL SUPPORT EMT WITHIN 3' EACH BOX, MC CABLE WITHIN 12" PER N.E.C. | |
01/06/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* |