Permit: T01CM05977

Parcel: 138030470

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/06/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/03/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ NEED TO VERIFY ELECTRICAL CONTRACTOR. / 1) NEED TO STRAP ALL ROMEX NOT SECURED TO STUDS. 2) ALL PLASTIC BOXES CANNOT BE MOUNTED THRU INSIDE WITH SCREWS. 3) GFI IN ENTRY WAY MISSING - PLAN CALLS FOR ONE IN ENTRY AND GARAGE. 4) WALL BEHIND SERVICE NEEDS TO BE INSTALLED AND WIRING SECURED TO IT.