Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM05971
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL FOR FOLLOWING UNITS: 16103 16102 16203 16202 16303 16302 16301 16201 ON ROOFTOP 1. FLEX TO BE SECURED WITHIN 12" OF TERMINATIONS AND ARRANGE TO PREVENT TRIPPING HAZARD MAX OVER CURRENT TO BE AS MARKED ON MANU. NAMEPLATE MAKE SURE HVAC EQUIPMENT CORRECTLY IDENTIFIED IN PANEL & ROOFTOP. |
|
| 01/29/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |