Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM05969
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. HAVE PLUMBER CHECK W & O ON TWO UNITS OK TO COVER 2. YARDWATER INSTALLED W/O INSPECTION CONTRACTOR POTHOLED PIPING CONNECTIONS LOOK OK |
|
| 12/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HALF OF 1ST FLOOR TUBS OK |
|
| 06/26/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) FIRST FLOOR TUBS ARE NOT SER. ONE OF THE BOXOUTS IS FULL OF WATER, SUGGESTING THERE MAY BE A LEAK. DRY OUT BOX AND RETEST 2) PVC DWC THRU ROOF ( 3 FLOOR ) OK 3) COPPER WATER PIPING OK 4) CLOSET FLANGES OK 5) 2ND & 3RD FLOOR TUBS- OK NEED TO SEE FIRST FLOOR TUBS SET & TESTED. 6) OK TO COVER ALL WALLS AND CEILINGS. | |
| 06/25/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NO WATER TEST ON PVC 2) NO PRESSURE TEST ON COPPER 3) INSPECTION STOPPED | |
| 06/19/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* 1) WATER LINES MAY NOT CROSS OR RUN ABOVE AN ELECTRICAL SERVICE PANEL. 2) NO TUBS SET. 3) ALL HANGERS AND SUPPORTS TO BE IN ACCORDANCE TO TABLE 3-1 94UPC 4) ALL BLDGS TO BE VISIBLY NUMBERED 5) INSPECTION INCOMPLETE |